AEGIS 2.0, XLT conventional single-hazard control units are designed for special hazard fire suppression environments Two enclosure options are available, one with a standard door and one with door mounted Manual Release and Abort switches
3 detection circuits, 2 supervisory circuits
Option to use SUP 1 as 4th detection circuit
1 Manual Release Circuit, 1 Abort Input
3 output for Bell, Siren, Strobe
2 Agent Release Circuits
3 Programmable and 1 Trouble Form-C Relays
1 Amp of auxiliary power at 24 VDC
Standard: UL, FM Approval, NFPA 72
Application: fire suppression control for FM200, Novec1230, CO2, InertGas, Sprinkler, Deluge, Pre-action and drencher
SIGMA XT Single Area, SIGMA XT+ Multi-Area (1 – 4)
Fire Extinguishant Control System
SIGMA XT Fire Extinguishant Control Panel
3 fire alarm zones + 1 fire extinguishing area
Built-in Manual Release Switch, Hold Switch
2 output for Bell, Horn/Strobe
24VDC output for solenoid
3 output for power shutdown, HVAC
Standard: EN12094-1, EN54-2 và EN54-4
MModel/Part#: K11031M2
SIGMA XT+ Fire Extiguishant Control Panel
Multi-Area Extinguishant
K21021M3: (2+1) - 2 fire alarm zones + 1 fire extinguishing area, 1 Manual Release Switch