Advance Delivery System ADS

Kidde Fire Systems
ADS™
Clean Agent Fire Suppression System
  • ADS (Advance Delivery System) with the patented-technology of “piston flow”, is capable of delivering greater mass flow rates 2.5 to 3 times faster than a ECS system. This innovation allows networking of longer pipe runs in complex configurations with smaller pipe sizes for protection of larger hazard areas.
  • Standard: UL, FM Approval
  • Application: applied for large areas, multi areas, long distance from the hazard to containers, complex piping arrangement
  • ADS FM200
  • Cylinder Pressure: 25 bar (360 psi)
  • All Cylinder Type (lbs/kg): 225 (102), 395 (179), 679 (306), 1010 (458)
  • Nitrogen Driver Cylinder: 124 bar (1800 psi): 2300 cu. in. (37,7 L), 4070 cu. in. (66,7 L), 4890 cu. in. (80 L)
  • ADS Novec1230
  • Cylinder Pressure: 25 bar (360 psi)
  • All Cylinder Type (lbs/kg): 200 (90,7), 350 (158,7), 600 (272,1), 900 (408)
  • Nitrogen Driver Cylinder 124 bar (1800 psi): 2300 cu. in. (37,7 L), 4070 cu. in. (66,7 L), 4890 cu. in. (80 L)
ADS FM200 in Formosa Ha Tinh Factory
Typical ADS™ Fire Suppression System
for Central Control Room
  1. 1. Smoke and Heat Detector (ceiling and access floor)
  2. 2. Fire Suppression Control Panel
  3. 3. Bell, Horn and Strobe
  1. 4. Clean Agent Cylinder (FM200 or Novec1230
  2. 5. Nitrogen Driver Cylinder
  3. 6. Discharge Nozzle (ceiling and access floor)